MD-RT1

RTD Temperature Intrinsic Safety Barrier (1-Channel)
The MD-RT isolated barrier is designed to measure the temperature of devices installed in hazardous areas, so as to promote intrinsic safety. This is achieved by preventing excess energy from possible faults on the safe side from reaching the hazardous area. Featuring up to three channels, it supports analog signals and can be configured with the Modbus protocol. The MD-RT1 is a 1-channel isolated barrier that also measures the temperature of 2-3-4 wire RTDs. And it supports various types of RTDs, including PT10, PT50, PT100, PT200, PT500, PT1000. Since it is installed in a safe area, measured values in hazardous areas are transmitted back to the safe area through the MODBUS – RTU protocol, with a bit rate up to 115.2 kbps for Monitor/ Configuration. Also, loop monitoring measures faults like sensor breakages and sensor shortages of the device and warns users by fault LED. Furthermore, the MD-RT consumes about 208 mA and 5W current. The power dissipation is less than 1W. The environmental conditions are -20 to +60 °C as an operation and -25 to +65 °C as storage temperature.
Product Features
  • Support 1 Channels
  • 24 VDC Supply
  • Analog Signal Type
  • Modbus RTU
  • RS-485 Interface
  • Connection with Screw Terminals
  • Configurable with Modbus Protocol
  • Measuring Temperature from RTDs
GENERAL SPECIFICATION
Signal TypeAnalog Input
Number of Channels1 Channel
SUPPLY
Rated Voltage24 VDC Nom (20-30 VDC) Reverse Polarity Protected
ConnectionTerminal 1 PIN 1(+24 VDC), Terminal 1 PIN 2 (GND)
Power Dissipation< 1 W
Current ConsumptionApprox. 208mA
Max. Power Consumption5 W
INPUT
Input2-3-4 Wire RTD
ConnectionTerminals 2
Rated Values-
Integration Time400 ms
Input Range0-4 kΩ (RTD/res)
RTD
RTD(PT10,PT50,PT100,PT500,PT1000)
Type of Measuring2,3 and 4 Wire
Measurement Loop MonitoringSensor Breakage
Measuring RTD Current323 μA
DEVIATION
RTDMax 0.1% of Span
DATA CONNECTION
Modbus RTURS-485 connection up to 115.2 kbps for Monitor/ Configuration
ConnectionTerminal1 PIN 3 (D-), Terminal1 PIN 4 (D+)
ISOLATION
Input / Power Supply1500 VDC
Example. safe electrical isolation by reinforced insulation according to IEC/EN 61010^-1
Rated insulation voltage 300 Veff test voltage 3 kV, 50 Hz, 1 min.
ENVIRONMENTAL CONDITIONS
Operation TemperatureTemperature Limits –20 to +60 °C
Storage TemperatureTemperature Limits –25 to +65 °C
MOUNTING
MountingOn 35 mm DIN Mounting Rail Acc. to EN 60715:2001
APPROVALS
IEC60079-0, IEC60079-11, IEC60079-15
FM & FM-C No.3024643,3029921C,conforms to Class 3600,3610,3611,3810
LOCATION
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D
Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation
SAFETY DESCRIPTION
ATEXII 1 G Ex ic [ia Ga] IIC T4 Gc, II 3 G Ex ic [ic] IIC T4 Gc, II 1 D Ex ic [ia IIIC Da] IIC Gc
II 3 D Ex ic [ic IIIC Dc] IIC Gc
IECExEx ic [ia Ga] IIC T4 Gc, Ex ic [ic] IIC T4 Gc, Ex ic [ia IIIC Da] IIC Gc, Ex ic [ic IIIC Dc] IIC Gc
FMClass 1, Zone 2 AEx ic [ia Ga] IIC T4 Gc, Class I, Zone 2 AEx [ic] IIC T4 Gc
Zone 20 Ex ic [ia IIIC Da] IIC Gc, Zone 2 Ex ic [ic IIIC Dc] IIC Gc
North American ZonesClass I, Division 2, Groups A, B, C, D T4, Class II, Division 2, Groups F, G
ASSOCIATED ELECTRICAL APPARATUS
Vo/Voc17.0 V, Io/Isc = 85 mA, Po/Po = 1.45 W
IECEx24V, Ci = 6 nF, Li = 0 nH. Um = 30 V, -20 °C ≤ Ta ≤ 60°C.