| Software | |
| OS | Linux Debian |
| Protocols | Modbus RTU Master/Slave Modbus TCP Server/Client IEC-104 CANopen OPC UA |
| OPC UA | |
| Development | IEC 61131-3 (Codesys) |
| Main Unit | |
| CPU | ARM® Cortex®-A8 up to 1GHz |
| RAM | 1GB DDR3 |
| Storage | 128 KB EEPROM, 4GB micro SD, 16GB EMCC |
| Watchdog Timer | Yes |
| I/O | |
| Digital Input | 2 Channels |
| Type | Dry Contact |
| Voltage Level | ON: +24 ~ +36 VDC OFF: 0 ~ +12 VDC |
| Connection | Terminals 13, 14 and 15, 16 |
| Analog Input | 2 Channels |
| Voltage & Current Input | ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA |
| Connection | Terminals 5-, 6+ and 7+, 8- |
| Display | |
| Signal | Micro HDMI |
| Resolution | 640 × 480, 800 × 480, 800 ×600, 1024 × 768 |
| COM Ports | |
| Ports | 1 × RS-232, 1 × RS-422/485 |
| Connection | RS-232: terminals 1(RX), 2(TX), 3(GND), 4(GND) RS-422: terminals 17(B-), 18(A+), 19(Y+), 20(Z-) |
| Ethernet | |
| Ports | 2 x RJ-45,10/100/1000 Base-TX ( Auto-negotiating, Auto MDI/MDI-X, LED indicators) |
| USB | |
| Ports | 1 x USB type A, 1 x mini USB type B1 x CANopen |
| CANopen | |
| Ports | 1 x CANopen |
| Connection | Terminals 9(CAN +), 10(CAN -) |
| Environmental Conditions | |
| Operation Temperature | Temperature limits –20 to +60 °C |
| Supply | |
| Rated voltage | 24 VDC nom (20-30 VDC) reverse polarity protected |
| Connection | Terminal 11(+24VDC), Terminal 12(GND) |
| Mounting | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 SAG Programmable Automation Controller - Linux base |